Skip to content
Christmas 2026: we are closing our installation schedule. Request your quote soon.
Very N'Ice
Ice rink chillers installed outdoors, with white insulated connection pipes

Ice rink energy consumption

An ice rink uses in the order of 2 to 3 kWh per m² per day: a Swedish study of indoor arenas measured an average of 2.2 kWh (range 1.5 to 4), and our calculator uses 3 kWh as a cautious figure. On that basis, a 200 m² rink open for 6 weeks uses around 25,200 kWh, about €4,500 at €0.18/kWh.

Written by Very N'Ice technical team · Updated October 2026

How much electricity an ice rink uses: benchmark figures

There is no single consumption figure, but there are published ranges:

Source Consumption Context
Rogstam, 2010, via IIR Average 2.2 kWh per m² per day; range 1.5 to 4 Indoor ice arenas in Sweden, total building consumption
Xtraice (synthetic ice manufacturer) Around 3 kWh per m² per day Average it publishes for real ice rinks
Very N’Ice calculator 3 kWh per m² per day Cautious assumption for temporary rinks

The Swedish study measures permanent indoor arenas, where refrigeration accounts for 35 to 75% of total consumption. A temporary outdoor rink is more exposed to sun and wind, which is why we use 3 kWh rather than 2.2.

Electricity cost by rink size

At 3 kWh per m² per day over a 6-week season (42 days):

Rink kWh per day kWh over 6 weeks Cost at €0.18/kWh Cost at €0.25/kWh
10 x 10 m (100 m²) 300 12,600 €2,268 €3,150
10 x 20 m (200 m²) 600 25,200 €4,536 €6,300
15 x 30 m (450 m²) 1,350 56,700 €10,206 €14,175
20 x 30 m (600 m²) 1,800 75,600 €13,608 €18,900
20 x 40 m (800 m²) 2,400 100,800 €18,144 €25,200

These are indicative calculations. Actual consumption may be lower for a covered rink in winter or higher for a rink in hot sun.

A measured reference from a Very N’Ice rink

A 300 m² Very N’Ice rink draws 80 to 100 amps on a 380-volt three-phase supply. That is equivalent to about 53 to 66 kVA of apparent power (√3 × 380 V × 80 to 100 A).

Another real measurement: a 15 x 25 m (375 m²) rink at an ambient temperature of 28 °C drew 83, 91 and 82 amps on its three phases. The 91 A phase also powered the rink’s lights and sound.

This is the demand with the chiller at full load, not the daily average. The chiller starts and stops by itself as the ice requires, and in winter it can sit idle for hours. So daily consumption is well below that power multiplied by 24 hours. The figure is mainly useful for sizing the electrical supply, which we calculate for every project (see technical requirements).

What pushes consumption up

Factor Effect
Direct sun The biggest heat load outdoors
Air temperature and humidity More heat and condensation to remove
Wind Increases heat exchange over the ice
Uncovered rink Exposed to sun, wind and rain
Uninsulated ground under the rink Cold is lost freezing the ground
Manifolds outside the rink They freeze the air instead of the ice
Uninsulated pipes They ice up and lose cold along the way
Plant far from the rink Longer pipes, greater losses
Ice too thick More mass to cool

Why the Very N’Ice system uses less

At Very N’Ice we treat the rink and the plant as a single machine: the energy that goes in should come out as cold on the ice, with minimal losses. Our freezing system was designed for that:

  • Insulating board under the cooling floor: the cold goes upwards, where the ice forms, not into the ground.
  • Manifolds inside the ice: the pipes that distribute the coolant also produce cold. Only two insulated pipes leave the rink.
  • Tempered aluminium pipework with 2 mm walls: aluminium conducts heat very well and does not leak.
  • Double insulation and propylene glycol as the coolant.

You can see the result on the chiller display: less than 1 °C difference between flow and return temperature. In our observation, traditional systems lose 3 to 5 °C. With this design, Very N’Ice states electricity consumption at least 40% lower than traditional systems, and guarantees it in writing in the contract.

Applied to the table above, a 40% saving on €10,206 for a 450 m² rink would be around €4,000 over a 6-week season. This is an estimate based on our consumption assumption, not a measurement.

How to reduce your rink’s consumption

  1. Cover it. A marquee that shades the whole ice surface is the single biggest saving outdoors.
  2. Place the plant close to the rink. If that is not possible, use pipes with reinforced insulation.
  3. Insist on insulation under the cooling floor and manifolds inside the rink. When comparing bids, ask about both.
  4. Keep the ice thin. Clearing snow and flooding with a very thin layer stops the ice building up and the plant cooling extra mass.
  5. Do not switch the plant off at night. The chiller already regulates itself; switching it off means recovering the ice afterwards.
  6. Service the plant every 6 months (oil and refrigerant levels) so it runs at full efficiency.
  7. Negotiate your electricity tariff before the season: the price per kWh matters as much as consumption.

If electrical power is the constraint

We only work with real ice, so the rink always needs cooling. If the available power is tight or the kWh is very expensive, what helps most is adjusting the ice area, covering the rink and looking after the insulation. We review this with you before sizing the chiller and the electrical supply (see technical requirements).

To find out what your specific rink would use, tell us the location, size, dates and whether it will be covered. Request a quote or try your figures first in the profitability calculator.

Frequently asked questions

How much electricity does an ice rink use per day?

In the order of 2 to 3 kWh per m² per day. A study of Swedish ice arenas (Rogstam, 2010) measured an average of 2.2 kWh per m² per day, with a range of 1.5 to 4. Our calculator uses 3 kWh per m² per day: a 200 m² rink would use around 600 kWh a day. The real figure depends on the weather and whether the rink is covered.

How much does it cost to power an ice rink?

At 3 kWh per m² per day and €0.18/kWh, a 6-week season costs around €2,270 for a 100 m² rink, €4,536 for a 200 m² rink and €10,206 for a 450 m² rink. Change the kWh price to your own tariff in the calculator to adjust the figure.

What electrical supply does an ice rink need?

We calculate it for each project because it depends on size, climate and cover. As a measured reference, a 300 m² Very N'Ice rink draws 80 to 100 amps on a 380-volt three-phase supply, about 53 to 66 kVA of apparent power. A three-phase supply with earth is always required.

Can I switch the ice rink off at night to save energy?

No. The hydraulic pump must run continuously and the chiller switches itself on and off, like a fridge, as the ice requires. In winter it is normal for the chiller to sit idle for hours because the ice needs no cooling. Switching the plant off manually damages the ice and means recovering it afterwards.

How much does the Very N'Ice system save?

Very N'Ice states consumption at least 40% lower than traditional systems and guarantees it in writing in the contract. The saving comes from insulation: an insulating board under the cooling floor, manifolds inside the ice, insulated pipes and a difference of less than 1 °C between chiller flow and return.

Have a project in mind?

Tell us the location, dates and size. We reply with a concrete proposal within 24 working hours.

WhatsAppQuote